BECKETT
GENISYS 7505
120V OIL BURNER CONTROL
7505B1500U
GeniSys™ 7505 120V Oil Burner Control
The Beckett GeniSys™ Advanced Burner Control is a 120 VAC primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications. The GeniSys™ is used with a suitable cad cell flame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 VAC thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats. It can provide interrupted or intermittent duty ignition, and it has a 15 second lockout time.
Features & Benefits
Water Resistant
Thermostat and boiler control compatible
Customizable pre-time and post-time
Three status lights for system monitoring and diagnostics
Welded relay protection with redundant motor relays
Limited reset and limited recycle
Sleek, modern design
Technician Pump Prime mode
5-Year Warranty
7505a replaces Honeywell R8184G
7505b replaces Honeywell R7184B
Two communication ports for adding alarm contacts, programming display, and/or future wireless communications
Technical Information
Voltage: 102 to 132 VAC
Current: 100 mA plus burner motor, igniter, and valve loads
Frequency: 60 Hz
Motor: 120 VAC, 10 full load amps (FLA), 60 locked rotor amps (LRA)
Igniter: 120 VAC, 3 A @ 0.7 PF min
Solenoid Valve: 120 VAC, 1 A @ 0.7 PF min
Thermostat Anticipator Current: 0.1 A
Thermostat Voltage: 24 VAC
Storage and Operating Ambient Temperature: -4°F to +150°F (-20°C to +65°C)
Moisture: 5-85% RH, non-condensing and non-crystallizing
Approvals: Underwriters Laboratory Recognition per UL372 and UL1998, and CSA-B140.0